The investigation report on the fire that killed three people in Fengtai, Beijing was published, suggesting that eight public officials should be held accountable.

  On November 22nd, the official website of Beijing Emergency Management Bureau released the investigation report on the fire and explosion accident of Fengtai District Energy Storage Power Station.

  At about 11: 50 on April 16th, a fire broke out in the light storage and charging integration project of Beijing Fuweisi Oil&Gas Technology Co., Ltd. (hereinafter referred to as Fuweisi Oil&Gas Company) located at No.14 Ximachang, Fengtai District. One person was killed, two firefighters were killed and one firefighter was injured, and the direct property loss caused by the fire was 16.6081 million yuan.

  According to the report, the direct cause of the fire in the south building is the internal short circuit fault of the lithium iron phosphate battery in the west battery room, which caused the battery to get out of control and catch fire. The direct cause of the explosion in the North Building was the internal short circuit fault of the single lithium iron phosphate battery in the battery room of the South Building, which caused the battery and battery module to spread out of control and catch fire. The flammable and explosive components generated by the accident entered the energy storage room of the North Building through the cable trench and spread, and mixed with air to form explosive gas, which exploded when it met with electric sparks.

  According to the suggestion of accident accountability, the owner unit responsible for the project investment and construction, and the procurement and installation of photovoltaic, energy storage and charging facilities — — The legal representative, logistics supervisor, operation and maintenance staff of Fuweisi Oil&Gas Company are directly responsible for the accident, and have been arrested by Fengtai District People’s Procuratorate for being suspected of serious accident.

  The main contents of the investigation report on the "4 16" major fire accident in Fengtai District are as follows:

  I. Basic information

  (I) The incident occurred at No.14, Ximachang, Fengtai District. The land use right owner and the property owner were Beijing Shoudai Baoli Industry & Trade Co., Ltd., which obtained the property ownership certificate in April 2004, with a construction area of 56,950.3 square meters; In March 2009, the state-owned land use right certificate was obtained. The land type is industrial land, the type of use right is allocation, and the land use right area is 200,363.92 square meters.

  In January 2004, Beijing Dinghuiqiao Jimei Furniture City Market Co., Ltd., a subsidiary of Beijing Jimei Home Market Co., Ltd. (hereinafter referred to as Jimei Home Company), successively rented all the buildings and venues in the courtyard of No.14 Ximachang in Fengtai District to operate Jimei Home Dahong Store. Before the incident, the construction area was increased to 208,102.55 square meters after renovation and expansion. There are 8 venues and other supporting buildings in the courtyard of Jimei Home Dahongmen Store. The incident building is located in the east courtyard of Hall 1, which mainly includes two brick-concrete structures, the North Building and the South Building, and an outdoor underground cable trench is built between the North Building and the South Building.

  The North Building is a two-story building with a building area of about 1060 square meters. The first floor is the energy storage room and equipment room of the optical storage and charging integration project, the 35kV transformer room, 6kV power distribution room and power distribution duty room used by Jimei Home Company, and the second floor is the 35kV control cabinet room of Jimei Home Company. Among them: the 6 kV distribution room has an east-west main cable trench and a distribution cabinet; There are two east-west cable ducts and four battery cabinets (56 battery clusters in total, using cylindrical lithium iron phosphate batteries) in the energy storage room.

  The South Building is a first-floor building with a building area of about 245.6 square meters, including the control room, lobby and maintenance room, west battery room, east battery room and equipment room. The control room is partially equipped with two floors. Twelve groups of battery cabinets (48 rows of battery clusters, using square lithium iron phosphate batteries) are installed in the west battery room, and 12 groups of battery cabinets (48 rows of battery clusters, using cylindrical lithium iron phosphate batteries) are installed in the east battery room. The cables at the bottom of the battery cabinets are gathered in the cable interlayer and enter the outdoor underground cable trench.

  The outdoor underground cable trench between the north and south buildings is 24 meters long and 1 meter wide, with the bottom 1.6 meters from the ground and the top 0.4 meters from the ground. 29 cables are laid in the trench; There is a ventilation shaft 3.7 meters away from the North Building. The cable trench enters the underground of the north building under the fifth window from the west to the east of the south wall of the north building, and enters the cable interlayer of the south building on the east side of the north gate of the south building.

  (II) Working principle of the electrical system of the incident project The electrical system of the incident project is divided into DC side and AC side, and the bidirectional conversion between AC and DC is realized through the power conversion system (PCS). On the AC side, there are mainly commercial power and merchants of Jimei Home Dahongmen Store. The DC side mainly includes photovoltaic power generation equipment, energy storage equipment and charging piles.

  During the day, photovoltaic power generation equipment gives priority to the merchants of Jimei Home Dahongmen Store, and the excess electricity can supply power to energy storage equipment and charging piles, and the energy storage equipment can also supply power to merchants; When the photovoltaic and energy storage equipment can’t meet the power demand, the commercial power can also be directly used. At night, energy storage batteries and charging piles are charged with trough electricity price.

  (3) Information of accident-related units

  1. Fuweisi Oil and Gas Company, with unified social credit code of 911101096843614396, legal representative Liu Bo, and other limited liability companies, was established on January 13, 2009, and its registered address is Room 389, No.3 Binhe South Road, Mentougou District, Beijing; The business scope includes electrical automation system, energy storage charging system, AC/DC hybrid microgrid system design, etc. Hefei Guoxuan Hi-Tech Power Energy Co., Ltd., Liu Bo (individual), Beijing Fuweisi Investment Management Center (Liu Bo Holdings) and other individuals hold about 40%, 33%, 24% and 3% respectively. In August 2018, Fuweisi Oil&Gas Company and Hefei Xuanyi Investment Management Co., Ltd. jointly established Beijing Guoxuan Fuweisi Optical Storage and Charging Technology Co., Ltd. (hereinafter referred to as Guoxuan Fuweisi Company), which holds some assets of the project, and the legal representative is Liu Bo, with no organization and personnel.

  2. Beijing Jingfeng Guowei Comprehensive Energy Co., Ltd. (hereinafter referred to as Jingfeng Guowei Company), with unified social credit code of 91110106MA01TA0N1B, legal representative Cui Lipei, and other limited liability companies, was established on July 1, 2020, and its registered address is BK003, 1st floor, Building 155, No.14, Dahongmen West Racecourse, Yongwai, Fengtai District, Beijing; The business scope includes power supply, solar power generation, centralized fast charging station, solar power generation technical services, etc. The company is jointly established by Beijing Jingtong Guoyou New Energy Co., Ltd. and Forvis Oil and Gas Company.

  3. Beijing Fengxin Electric Engineering Co., Ltd. (hereinafter referred to as Fengxin Electric Company), with the unified social credit code of 91110106102173826J, legal representative wang pu, is a limited liability company (invested or controlled by natural persons), and was established on January 19, 1988 with the registered address of Building 22, No.28, Lugouqiao Farm Road, Fengtai District, Beijing. Its business scope includes professional contracting, etc. The company has the qualifications of building decoration engineering professional contracting level 2 and power transmission and transformation engineering professional contracting level 3.

  (4) Construction of the incident project

  The incident project is constructed in two phases, and the main equipment includes photovoltaic modules, energy storage battery clusters, energy storage containers and charging piles.

  1. Construction of the first phase of the project

  In October 2017, Fuweisi Oil&Gas Company and Beijing Pinggaoqing Great Technology Development Co., Ltd. signed a cooperation agreement with Jimei Home Furnishing Company, which is responsible for providing installation and operation sites and enjoying preferential electricity prices for the project; Fuweisi Oil&Gas Company is responsible for the investment and construction of the project and the procurement and installation of photovoltaic, energy storage and charging facilities, and the ownership of related facilities belongs to the company; Beijing Pinggaoqing Great Technology Development Co., Ltd. (withdrawn from the project in August 2020) is responsible for the renovation of the 6 kV distribution room, purchasing and installing the energy storage control system and equipment, assisting in the project filing, photovoltaic grid connection and leading the application for relevant subsidies.

  In March 2018, Beijing Jingdian Xunjie Power Technology Co., Ltd. issued the design drawings of the 6 kV distribution room reconstruction project of Jimei Home Dahongmen Store, and Fengxin Electric Company carried out civil and electrical construction.

  In April 2019, the first phase of the project was officially put into operation. The equipment mainly includes 1.4 MW roof distributed photovoltaic, 4 MW /12 MW energy storage and charging piles.

  2. Construction of the second phase of the project

  In May 2020, Fengxin Electric Company upgraded the energy storage in the second phase of the incident project, which involved the battery room, equipment room and outdoor underground cable trench in the south building. Before the incident, 2 MW /28 MWh energy storage has been built. In July, Fuweisi Oil and Gas Company and Beijing Jingtong Guoyou New Energy Co., Ltd. registered and established Jingfeng Guowei Company, which was responsible for the photovoltaic construction of the second phase of the incident project and the acquisition of the assets of the incident project held by Fuweisi Oil and Gas Company and Guoxuan Fuweisi Company; Jingfeng Guowei Company signed energy use agreement and site use agreement with Jimei Home Furnishing Company and other units. In November, Jingfeng Guowei Company entrusted Sichuan Hualun Power Engineering Co., Ltd. to arrange a 1.6 MW distributed photovoltaic power generation system on part of the roof of Jimei Home Dahongmen Store; In January 2021, the photovoltaic module was installed and was being debugged before the incident.

  After investigation, the batteries used in the incident project were all produced by Hefei Guoxuan Hi-Tech Power Energy Co., Ltd., and battery testing materials were provided. Before the incident, Jingfeng Guowei Company had carried out the asset evaluation work related to the incident project, and had not yet completed the asset acquisition and delivery.

  As of the time of the incident, the electricity generated by the project was used by Jimei Home Dahongmen Store; From March 2019 to March 2021, Jimei Home Furvis Company remitted about 9,329,900 yuan of electricity to its account.

  (five) the project record.

  In April 2018, Forvis Oil and Gas Company filed with Fengtai District Development and Reform Commission "Distributed Photovoltaic Power Generation Project of Jimei Home Dahongmen DC Photovoltaic Storage and Charging Integration Project" and "New Electric Vehicle Charging Pile Project of Jimei Home Dahongmen DC Photovoltaic Storage and Charging Integration Project" to build a 1.4 MW roof photovoltaic and carport photovoltaic system and a large-capacity DC charging pile.

  In September 2020, Jingfeng Guowei Company filed the "Jingfeng Guowei Integrated Smart Energy Jimei Dahongmen Distributed Photovoltaic Power Generation Project" with Fengtai District Development and Reform Commission to build a distributed photovoltaic power generation system with a capacity of 40,000 square meters and 4 MW.

  In December 2020, Jingfeng Guowei Company filed the "Jingfeng Guowei Integrated Smart Energy Jimei Dahongmen Energy Storage Project" with Fengtai District Development and Reform Commission, and built a 10 MW /40 MWh energy storage power station system. After verification by Fengtai District Development and Reform Commission, the project was not implemented. On July 19th, 2021, Jingfeng Guowei Company has voluntarily cancelled the project filing through the online filing management system of Beijing enterprise investment projects.

  In addition, after verification by Fengtai District Development and Reform Commission, the built energy storage projects involved in the accident belong to unprepared projects.

  Second, the accident and emergency rescue situation

  (a) the accident.

  At about 11: 50 on April 16th, 2021, five people, including Xie Xialing of Sichuan Hualun Electric Power Engineering Co., Ltd., went to the South Building to check the renovation progress of the control room, and found that the battery cabinet on the south side of the west battery room of the South Building caught fire and smoked, and immediately used the on-site fire extinguisher to dispose of it. Xie Xialing telephoned Liu Bo, the person in charge of Fuweisi Oil and Gas Company.

  At about 12: 13, Liu Bo led Chen Yuanzhong and others to the scene and took fire extinguishers from the South Building and the North Building to participate in the fire fighting. Because the open flame was extinguished and continued to rekindle, Liu Bo assigned Chen Yuanzhong to the energy storage room of the North Building to cut off the AC side. Connect with the energy storage system and disable the photovoltaic system. At 12: 17, Liu Bo called the police. At about 12: 20, Liu Bo entered the North Building and told Luo Guangjun, the electrician on duty in Jimei Home Furnishing Company, to turn off the switch between the 6 kV distribution cabinet and the energy storage equipment.

  At about 13: 40, Liu Zhange, an electrician of Jimei Home Furnishing Company, arrived at the duty room of the North Building and went to the 6 kV distribution room with Luo Guangjun to confirm that the switch between the distribution cabinet and the energy storage equipment had been disconnected. During the period, a large amount of smoke emerged from the south building, accompanied by deflagration from time to time.

  At about 13: 45, Liu Zhange went to the hospital to check and found that Liu Bo and firefighters were injecting water into the outdoor underground cable trench, and then went to the 6 kV distribution room in the north building to check and found that the cable trench was full of white smoke, no accumulated water and a pungent smell. At about 14: 13, an explosion occurred in the North Building.

  (2) Emergency rescue situation

  After receiving the alarm, the 119 Combat Command Center of the Municipal Fire and Rescue Corps dispatched 47 fire engines and 235 officers and men to the scene for disposal. City, district public security organs and emergency management, electric power, sanitation, ecological environment, health and other departments were present for collaborative disposal.

  At 12: 24, firefighters arrived at the scene and found that the battery in the west battery room of the South Building was on fire, accompanied by explosions from time to time. No open fire was found in the east battery room, and there were no trapped people at the scene. Immediately, fire fighting and rescue were carried out, and water guns were deployed in the periphery to prevent the fire from spreading.

  At 14: 13: 16, an explosion occurred in the North Building, causing one electrician on duty to die, two firefighters to die and one firefighter to be injured. At 23: 40, the open flame was completely extinguished and the site was continuously cooled for 40 hours. At 16: 21 on April 18th, the site was cleared.

  (3) Direct property losses caused by fire

  The price was confirmed by Beijing Fengtai District Price Certification Center, and the statistics of Fengtai District Fire Rescue Agency confirmed that the direct property loss of this fire was 16,608,100 yuan.

  Third, the cause and nature of the accident

  (A) the direct cause

  The public security organs combined with the analysis of on-the-spot investigation, investigation and interrogation,Exclude the suspicion of intentional criminal offence.

  1. On-site inspection

  After on-site inspection by fire rescue agencies, the battery cabinet in the west battery room of the South Building was over-fired, and the roof directly above the battery cabinet in the fifth group from west to east on the south side was burned and cracked, and the concrete part of the top floor was missing. The battery cabinet area had the characteristics of initial fire. Combined with the testimony of relevant witnesses, it is determined that the fire site of the South Building is located at the battery cluster at the north end of the fifth battery cabinet, from the south side of the west battery room to the east, at the battery modules on the 8 th to 10 th floors from bottom to top.

  The walls on the east and west sides of the energy storage room in the north building were blown up and flew out, all the window glasses on the south side were destroyed, and the upper floor partially collapsed; The indoor energy storage converter, control cabinet and battery cabinet are dumped to the south as a whole; The deformation of the lower end of the battery cabinet in the second group from west to east is the most serious, and the steel beam between the battery cabinet base and the cable trench (the connection is not blocked) is more bent upward than the other three groups of battery cabinets. In the battery management system of 7 clusters of battery cabinets in this area, the components in the battery management system of the third cluster from west to east are scattered and displaced, the positive and negative relays have fallen off and the cover plate is missing, which is more serious than the other 6 clusters. It is determined that this is the initial ignition source position.

  There is a small amount of water at the bottom of the outdoor underground cable trench between the north and south buildings, and there are traces of smoke in the trench, and oily residues are deposited at the bottom; Some cables in the cable trench have traces of fire on their surfaces; The cable trench between the northern end of the cable trench and the cable trench in the north building is not tightly sealed, and there is a gap. There is no seal between the cable interlayer in the southern end and the south building.

  2. Detection and identification

  Appraised by Tianjin Fire Material Evidence Appraisal Center of Fire and Rescue Bureau of Emergency Management Department, the negative terminal of battery module on the 9th floor at the fire site of South Building has an internal short circuit fault in the innermost battery cell in the fifth row. The battery is a square battery, and the electrode material conforms to the characteristics of lithium iron phosphate battery.

  Tested by Beijing Physical and Chemical Analysis and Testing Center, the main components of the battery electrolyte of the same model in Nanlou provided by the battery supplier are a mixture of methyl ethyl carbonate, ethylene carbonate and phosphorus-containing inorganic salts; Methyl ethyl carbonate was detected in soil (muddy) and volatile organic compounds such as methyl ethyl carbonate and benzene series were detected in gas in outdoor underground cable trench.

  3. Experimental analysis and simulation.

  The battery safety laboratory of Tsinghua University Institute of Vehicles and Transportation conducted an experimental analysis on the square battery which was the first to break down in the South Building. The out-of-control battery will produce ejecta, mainly methyl ethyl carbonate vapor, hydrogen, methane, carbon monoxide, carbon dioxide and so on.

  The smoke simulation conducted by the Institute of Building Fire Prevention of China Academy of Building Research shows that after the south building caught fire, the smoke mixture (including the thermal runaway injection product of the lithium iron phosphate battery which was not fully burned) generated at the scene can enter the indoor cable trench of the north building through the outdoor underground cable trench. Before the explosion of the North Building, the concentration of flammable and explosive gas was about 31%, and the total amount was not less than 280 cubic meters.

  The explosion process was simulated by the State Key Laboratory of Explosion Science and Technology of Beijing Institute of Technology: when the flammable and explosive components (hydrogen, methane, carbon monoxide, methyl ethyl carbonate, etc.) in the North Building reached 200 cubic meters and were detonated by the ignition source in the energy storage room of the North Building, the explosion damage scene obtained by simulation was consistent with the accident scene, and the explosion equivalent was 26 kg TNT.

  4. Experts demonstrate and analyze the situation

  Based on the analysis of investigation, on-site inspection and physical evidence identification, it is found that the battery thermal runaway fire in the South Building is caused by the internal short circuit fault of lithium iron phosphate battery in the west battery room.

  Combined with the analysis of on-site video, on-site inspection and material evidence identification, the explosion of the North Building conforms to the characteristics of volume explosion, and it is determined that the explosion is gas explosion. The explosive substance in the North Building is the explosive gas formed by the mixture of flammable and explosive components in the thermal runaway injection product of the lithium iron phosphate battery in the South Building and air. The initiation point is located in the energy storage room of the North Building, excluding the factors of fire source caused by personnel activities and uncontrolled ignition of the battery, and it is determined that the ignition source is the electrical spark generated in the energy storage room.

  After analysis, the smoke containing the thermal runaway injection product of lithium iron phosphate battery diffused from the outdoor underground cable trench into the north building, and entered the battery system with high voltage (nominal 720 volts) DC charged state, which led to the action of the relay (located at the bottom of the battery cabinet) to generate electrical sparks.

  5. The direct cause of the accident

  According to the on-site inspection, testing and identification, experimental analysis, simulation and expert argumentation of fire rescue institutions, the investigation team comprehensively analyzed the direct causes of the accident as follows:

  The direct cause of the fire in the south building is the internal short circuit fault of the lithium iron phosphate battery in the west battery room, which caused the battery to get out of control and catch fire.

  The direct cause of the explosion in the North Building was the internal short circuit fault of the single lithium iron phosphate battery in the battery room of the South Building, which caused the battery and battery module to spread out of control and catch fire. The flammable and explosive components generated by the accident entered the energy storage room of the North Building through the cable trench and spread, and mixed with air to form explosive gas, which exploded when it met with electric sparks.

  (2) Indirect causes

  1. The responsibility of the safety subject of the enterprise involved is not implemented, and there is a problem of construction before filing in the construction process; Continue to operate in the event that the battery pack leaks, heats up and smokes many times in the incident area, but the safety hazards are not completely eliminated; The two ends of the outdoor underground cable trench between the north and south buildings were not effectively separated and blocked, and the accident emergency response plan was not formulated according to the actual risk of the site.

  2. It is not enough for the relevant units to study and deploy and supervise the implementation of safety supervision and inspection; The research on the high-quality development of new energy projects under the premise of ensuring safety is not deep; The investigation of safety hazards is not comprehensive and thorough, and the safety risks existing in the construction, operation and maintenance of the incident project are neglected and out of control.

  (3) Nature of the accident

  In view of the above analysis, according to the relevant national laws and regulations, the investigation team determined that the "4 16" large fire in Fengtai District was a liability accident.

  Iv. Suggestions on handling the responsible personnel and units of the accident.

  (1) Persons who propose to be investigated for criminal responsibility.

  1. Liu Bo, the legal representative of Forvis Oil&Gas Company, is directly responsible for the accident and is suspected of the crime of major liability accident. On May 24, 2021, Fengtai District People’s Procuratorate approved the arrest.

  2. Shuai Changsheng, the logistics supervisor of Forvis Oil and Gas Company, is directly responsible for the accident and is suspected of major liability accident. On May 24, 2021, Fengtai District People’s Procuratorate approved the arrest.

  3. Chen Yuanzhong, an employee of the operation and maintenance post of Forvis Oil and Gas Company, is directly responsible for the accident and is suspected of major liability accident. On May 24, 2021, Fengtai District People’s Procuratorate approved the arrest.

  (two) personnel and units that suggest accountability.

  1. Wang Xiaoli, Deputy Secretary and Office Director of Dahongmen Street Working Committee in Fengtai District. It is recommended to give a warning.

  2. Pang Xuming, member of the Working Committee of Dahongmen Street, Fengtai District, Minister of Armed Forces and Director of Ping An Construction Office. It is recommended to give administrative warning.

  3. Lu Yanbo, the chief of the Ping ‘an Construction Office of Dahongmen Street in Fengtai District, is also the captain of the full-time security officer inspection team of Dahongmen Street. It is recommended to give administrative records.

  4. Yi Pan, executive vice-captain and head of the first group of full-time security officer inspection team in Dahongmen Street, Fengtai District. It is suggested to give greater punishment to government affairs.

  5. Liu Lei, director of the Regulation Department of Fengtai District Development and Reform Commission, is the actual person in charge of work safety. It is recommended to give a warning.

  6. Du Mingyang, safety officer and captain of production safety inspection team of Regulation Section and Resource Conservation Section of Fengtai District Development and Reform Commission. It is recommended to give administrative warning.

  7. Zhou Fangming, Chief of Fire Prevention Supervision Section I of Fengtai District Fire Rescue Detachment (Chief of Law Enforcement Team I). It is recommended to give a warning.

  8. Li Chunliang, Deputy Chief of Fire Supervision Section I of Fengtai District Fire Rescue Detachment (Deputy Chief of Law Enforcement Team I). It is recommended to give administrative warning.

  At the same time, the Municipal Commission for Discipline Inspection and the Municipal Supervision Committee issued a work reminder letter to the Fengtai District Government for the illegal construction of houses on the plot where the incident occurred; Criticize, educate or talk to relevant public officials to solve the problem that the research on high-quality development of new energy projects is not deep under the premise of ensuring safety; The Fengtai District Commission for Discipline Inspection ordered the Dahongmen Street Working Committee and the Fengtai District Development and Reform Commission Party Group to make a written inspection.

  In addition, the superior unit of Jingfeng Guowei Company removed Cui Lipei from the post of executive director and legal representative of Jingfeng Guowei Company, gave Li Jingling an administrative warning, and dealt with two people accordingly.

  (three) units that suggest administrative punishment.

  1. Forvis Oil&Gas Company failed to find and eliminate fire hazards, and the fire rescue agency shall give administrative punishment according to relevant regulations.

  2. Jingfeng Guowei Company failed to formulate and implement fire safety management measures and fire safety operation procedures, and the fire rescue agency shall give administrative punishment according to relevant regulations.

  3. In view of the problems existing in the built energy storage projects involved in the accident, the development and reform department ordered Forvis Oil and Gas Company to rectify and deal with them according to the law and regulations.

  4. In view of the clues that the energy storage upgrading and reconstruction project of the incident project is suspected of being implemented without the design of a professional unit, the municipal planning and natural resources department will investigate and verify it and investigate and deal with relevant illegal acts according to law.

  In addition, the extended investigation by the Municipal Housing and Urban-Rural Development Committee found that Fengxin Electric Company was suspected of having problems such as imperfect safety production responsibility system, failure to set up independent safety production management institutions and insufficient full-time safety production management personnel, and it was planned to temporarily suspend its safety production license for 60 days; Some of the company’s qualifications no longer meet the requirements of the corresponding standards, and it is planned to order it to make corrections within a time limit. During the rectification period, it is not allowed to apply for qualification upgrades or additions, and it is not allowed to undertake new projects.

  V. Suggestions on accident rectification and preventive measures

  In order to draw a profound lesson from the accident, earnestly practice the concept of life first and safe development, and effectively prevent and resolutely curb similar accidents, the following suggestions and measures are put forward:

  (1) Strictly implement safety responsibilities. Jimei Home Furnishing Company should build and use leased premises and buildings according to laws and regulations, strengthen safety management, strengthen safety inspection and hidden dangers investigation and rectification. Forvis Oil and Gas Company should implement the fire safety responsibility system, improve the emergency response plan, strengthen safety education and safety inspection, and eliminate hidden dangers in time. Jingfeng Guowei Company should improve the company’s safety management system, strengthen distributed energy management, and carry out safety evaluation and inspection for installed roof photovoltaic.

  (two) improve the construction and operation management of electric energy storage facilities and places. The Municipal Emergency Bureau takes the lead, and gives guidance jointly with the departments of development and reform, urban management, planning of natural resources, housing and urban-rural construction, economy and informatization, market supervision, fire fighting and rescue, etc. The relevant district governments rely on professional institutions to conduct safety risk assessment of suspended energy storage power stations in this area, evaluate the risk level of suspended energy storage power stations, and put forward work opinions. The Municipal Development and Reform Commission takes the lead, and the Municipal Emergency Bureau cooperates with it to organize experts and professional institutions to re-examine the construction plan for all projects under construction and projects that have not been put into construction of energy storage power stations. Only after passing the assessment can the construction be carried out. The Municipal Urban Management Committee shall, together with relevant departments, formulate technical standards to standardize the design, construction, acceptance and operation management of electric energy storage facilities in this Municipality. The Municipal Market Supervision Bureau and the Municipal Bureau of Economy and Information Technology shall establish and improve the quality management system of batteries and their energy management systems in energy storage power stations.

  (3) Strengthen safety supervision and management. Fengtai District Government carried out a comprehensive survey of energy storage facilities in the whole region, established and dynamically updated basic accounts, and organized relevant departments to carry out comprehensive safety inspection and safety risk assessment. The Municipal Fire and Rescue Corps strengthened the fire supervision and inspection of electric energy storage places, formulated and improved the accident handling norms of energy storage power stations, strengthened the handling drills, and further improved the emergency rescue and handling work level of energy storage power stations.

  (4) Continue to promote safe development. Urban management, development and reform, fire rescue, emergency management and other departments and Fengtai District Government should firmly establish the concept of safe development, put the prevention and resolution of safety risks in an important position, standardize the location and layout of new energy storage, establish and improve the working mechanism of overall coordination and management of photovoltaic power generation applications, and strengthen the quality management and safety supervision of related projects; For the electric energy storage facilities that have been built and are under construction, strengthen comprehensive analysis and judgment, find problems in time, solve problems, and prevent accidents caused by out-of-control pipe leakage. Fengtai District Government should plan the planning and construction of Dahongmen area as a whole, promote the regional wholesale market in an orderly manner, and promote functional remodeling, industrial upgrading and quality improvement.